Abstract
AbstractThis paper proposes a novel and simple control method for the active power quality compensators (APQCs) used in electrified railways. The proposed method uses only the constant dc capacitor voltage control block, which is commonly used in the APQCs. No detection blocks of the harmonic, reactive, and negative‐sequence components are necessary. Thus we offer the simplest way to compensate the harmonic, reactive, and negative‐sequence currents on the primary side of the Scott transformer in the traction substation. The basic principle of the proposed control method is discussed in detail, and then confirmed by digital computer simulation usingPSIM software. A prototype experimental model is constructed and tested. Experimental results demonstrate that the balanced source currents with the unity power factor are obtained on the primary side with the proposed control method, which uses only the constant dc capacitor voltage control. Copyright © 2009 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEJ Transactions on Electrical and Electronic Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.