Abstract

Fouling of cooling tower fills is one of the most important factors affecting its thermal performance, which reduces cooling tower effectiveness and capability with time. In this paper, the fouling model presented in an earlier paper using the experimental data on fill fouling, is used to investigate the risk based thermal performance of the cooling tower. It is demonstrated that effectiveness of the cooling tower degrades significantly with time indicating that for a low risk level ( p=0.01), there is about 6.0% decrease in effectiveness for the given fouling model. The sensitivity analysis of the cooling tower is investigated for both rating and design calculation for different values of mass flow rate ratios. The effect of atmospheric pressure on the thermal performance of the cooling tower is also demonstrated.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call