Abstract
Four distinct uninterruptible power supply topologies are presented here for powering hybrid fiber/coaxial (HFC) networks. Topologies based on a low frequency isolation transformer are found to have better efficiency than the topologies with high frequency transformer. However, the latter topologies have much better performance in terms of transient response, quality of the output voltage, input power factor, total harmonic distortion of the input current, size and weight. The series-parallel resonant based UPS topology is found to have best overall performance for the emerging HFC applications.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.