Abstract

This paper experimentally verifies and compares two dynamic test methods for a calibrated hot box to characterize the transient thermal performance of complex walls. In these methods, a wall specimen is sandwiched between the two conditioning chambers of a calibrated hot box. The exterior surface of the wall specimen is subjected to a time-varying excitation function in air temperature. At the interior surface, the air temperature is maintained steady, and the heat transfer response is measured. Conduction transfer function coefficients that relate the measured heat transfer response to the excitation function are derived. The two dynamic test methods were applied to an insulated hollow concrete block wall that contained significant thermal bridges and lateral heat flows. Empirical transfer function coefficients derived by the test methods predicted with good agreement the heat transfer response of this wall specimen when its exterior surface was subjected to excitation functions that differed markedly from those used to derive the coefficients.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.