Abstract

This article describes the effects of two methods for representing the nonuniform distribution of flow properties across a steam turbine discharge annulus, on the hood loss coefficient. One method uses a mass-weighted integration of the property across the station, while the other is based on a mass-derived representative value of the property. The former has the potential for very high accuracy provided a sufficient number of points are integrated. The latter, while less accurate, is easier to apply and therefore more commonly used. The analytical modeling includes a simplistic step profile of pressure across the annulus, as well as a three-dimensional exhaust hood, flow-field simulation calculated using a Navier–Stokes code. Results show that significant errors can occur in the hood loss coefficient with the mass-derived approach. Although the analysis centers on hood loss coefficient as the performance parameter whose sensitivity is being monitored, the results highlight the pitfalls of improper application of measured data for any internal flow system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.