Abstract

Drainage measurements are commonly used for assessing the quality, water-retention ability and stability of aqueous foams used in fire-fighting applications. A new experimental technique is proposed in this paper, for measuring the drainage rate of liquid from compressed-air fire-fighting foams. The procedure outlined here provides advancement in precision over that prescribed by the standard for low expansion foams (NFPA 11, Standard for evaluating low expansion foams, NFPA, Quincy, MA, 1998). A comparative analysis of drainage characteristics in two commonly used Class B fire-fighting foams was undertaken, from theoretical and experimental perspectives: (i) aqueous film forming foam and (ii) film forming fluoroprotein foam. It is demonstrated that even though both the foam solutions exhibited similar fundamental physical properties, the disparities in surface rheological properties cause the resulting foams to have remarkably distinct drainage and coarsening characteristics. In addition, a drainage model is outlined, which allows the explicit prediction of the time evolution of liquid holdup profiles and drainage rates in fire-fighting foams. The existing drainage model is extended to simulate fire-fighting foams made from protein based and synthetically produced surfactants.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.