Abstract

The utility of entransy is considered for the performance assessment of an experimental desiccant cooling system, DCS in comparison with the energy and exergy analyses. An increase in the regeneration temperature TR is associated with a decrease in the sensible coefficient of performance COP which has a measurement range of 0.2≤COP≤1.3. The calculated magnitude of COP and system exergetic efficiency, ηDCS is 0.345 and 3.3% respectively. The desiccant wheel, DW has the greatest percentage of the total exergy destruction of DCS. Therefore an entransy effectiveness parameter of DW, ɛDW,ENTRANSY is introduced. This parameter expresses the sensible cooling capacity, CC as a ratio of heat input Q and the regeneration entransy stored in DW, EDW,R. ɛDW,ENTRANSY can be used as an alternative performance parameter since the dependence of ɛDW,ENTRANSY on TR is the same of COP. There exists an acceptable conformity between the calculated magnitudes of ɛDW,ENTRANSY and ηDCS. The cited similarity between the application of entransy and entropy generation is verified for the discussed case. However entransy is of considerable practical importance for the performance analysis of heat transfer processes.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.