Abstract
The development of DC grids faces challenges from DC fault protection. The conventional DC circuit breaker (DCCB) employs metal-oxide varistor (MOV) to isolate the faulted line, in which the fault isolation process is coupled with the energy dissipation process. In this study, a clamping type DCCB (CTCB) uses internal capacitors to clamp the converter voltage is proposed. Thanks to the proposed configuration, fault isolation and energy dissipation are decoupled, resulting in a fast fault isolation and low energy dissipation compared to the conventional DCCB. The working principle of the proposed CTCB is presented and verified in a DC grid simulation model. A comparison is made with the traditional DCCB. The fault isolation time can be reduced by 34.5 %. The dissipated energy can be reduced by 17.4 %. The energy dissipation power can be reduced by 76.2 %. <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">1</sup>
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.