Abstract
A computational fluid dynamics (CFD) program, Fluent V4, was used to predict natural ventilation rates and airflow patterns of a multi-span, sawtooth greenhouse for various roof and side vent openings and outside wind speeds. Predicted rates were found to be both well above and well below a standard volumetric air exchange rate of 1.0 A.C. min–1. The maximum and most acceptable ventilation rates were obtained with the combined use of a windward side vent and leeward roof vents on all multi-span sections. Ventilation rates ranged from 1.4 to 4.01 A.C. min–1 for the best two-span case and 0.14 to 2.0 A.C. min–1 for the similar four-span case for outside wind speeds of 0.5 and 2.0 m s–1, respectively. Predicted ventilation rates ranged from 0.17 to 0.7 A.C. min–1 when no side vent was used and the roof vents were fully open.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.