Abstract

A numerical model has been developed to investigate the contaminant removal and air freshness in a ventilated two-zone enclosure. The average contaminants and the distributions of air age in each zone under variable positions of door, supply and exhaust are compared. The correlation between the average contaminants and each of the main parameters, such as door location, supply and exhaust positions etc., are presented, and the average air ages in both zones are illustrated against door position. It is found that the average air age in the upstream zone is less affected by the door position than that in the downstream zone, and that the door position near the side-walls seems to give better air circulation. It is also concluded that the supply and door positions affect the concentration in the upstream zone significantly, while the exhaust location does not seem to influence the average concentration in either the upstream or the downstream zone.