Abstract

In a recent paper (G. Bargboer and A. P. J. van Deursen, IEEE Trans. Electromagn. Compat., vol. 52, no. 3, pp. 684-90, Aug. 2010) we dealt with current injection measurements to test the lightning protection system of a newly built pharmaceutical plant. In a tentative extrapolation, the measurements were extrapolated to actual lightning. Here, we extend the model and calculate the response of the installation on lightning currents and include resonances in the cable trays and test cables contained in it. It turned out that suspension rods between roof support and cable tray were indispensable to suppress the resonances. The time dependence of the present results and the earlier simplified model given in differ greatly, but the amplitudes of induced voltages appear to be of the same order of magnitude.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.