Abstract

Aiming at the problem that the content of acetylene and total hydrocarbons in the insulating oil exceeds the standard during the operation of a 110kV transformer, a bisection plane positioning method based on the UHF is used to accurately locate the partial discharge position. Secondly, the intermittent multi-point ground fault of the transformer core was found through the the windlass cover of the transformer, which successfully verified the accuracy of PD positioning. Finally, the reasons and process of discharge are discussed in depth.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.