Abstract
Simulating the grids cascading failure process is an essential means of preventing cascading failures. In traditional cascading failure models, DC power flow models are applied widely, but reactive power characteristic cannot be reflected. This study improves and applies an AC-based Cascading Failure model (called ACCF model), which captures bus load shedding and branch failures, all via AC power flow and optimal power flow analyses. Taking the IEEE 30- and 118-bus power systems as case studies, the ACCF model is proved feasible. With case studies, this study reveals that during the cascading failure, the broken branches are not necessarily close to the initial faulty elements, and some of the affected nodes/branches are “far” away from the initial faulty nodes. And as the initial branch failure probability increases, the system real power loss probability function gradually changes from approximate power distribution to a normal distribution. Meanwhile, the study also discovers that as the initial branch failure probability further increases, the system real power loss changes from a normal distribution to a distribution that appearing to be symmetric with the loss function under a low initial branch failure probability. The findings could facilitate grids safety and stable operation, as well as grids disaster prevention and relief.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Physica A: Statistical Mechanics and its Applications
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.