Abstract
Discontinuous pulse width modulation (DPWM) method is broadly used in three-phase inverter to achieve high efficiency through the reduction of the switching loss. The high-power rating photovoltaic (PV) inverter with DPWM has its intrinsic issues such as large DC-link voltage ripple and high-frequency resonant current due to the large stray capacitance proportional to the power rating. To extend the application of DPWM from 10 kW to 80 kW PV inverter, a new DPWM method (DPWMn) which divides the clamping period into <i>n</i> intervals is proposed to achieve the three objectives simultaneously: 1) reduction of the DC-link voltage ripple; 2) suppression of the high-frequency current oscillation; 3) improve the efficiency compared to the continuous space vector PWM (SVPWM). The proposed DPWMn is validated by an 80 kW three-phase T-type PV inverter. Compared to the SVPWM, the DPWMn has reduced 30% switching loss while maintaining the similar power quality and the common mode current. Compared to the existing DPWM methods, DPWMn reduces the voltage ripple by 52% and has the minimum energy ripples. Furthermore, the carrier-based DPWMn only utilizes the measured voltage and can be easily implemented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.