Abstract

In the manufacturing of power transformers, the impregnation of the solid electric insulation systems (cellulosic materials) with a dielectric liquid is a key issue for increasing the breakdown voltage of the insulation, and this prevents the apparition of partial discharges that deteriorate the insulation system. After introducing the problem, this article presents the theory of impregnation and later carries out a bibliographical review. Traditionally, mineral oils have been used as the dielectric liquid in electrical transformers, but for environmental (low biodegradability) and safety (low ignition temperature) reasons, since the mid-1980s, their substitution with other ester-type fluids has been studied. However, these liquids have some drawbacks, including their higher viscosity (especially at low temperatures). This property, among other aspects, makes the impregnation of cellulosic materials, which is part of the transformer manufacturing process, difficult, and therefore this tends to lengthen the manufacturing times of these machines.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.