Abstract

Introduction: Re-RT is considered an option for recurrent HNC. In this scenario, it is important to accurately estimate the initial treatment dose received by the critical organs (OARs). Deformable image registration (DIR) could improve this accuracy.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.