Abstract

Transformer energization tests were performed in Hydro-Québec Chateauguay substation on a 300 MVA single-phase 765/125/12.5kV Yg-Yg-Δ power transformer in order to improve power transformer modeling for harmonic over-voltage evaluations upon energizations and fault removals close to HVDC converters with associated filters and capacitor banks. From these results, an enhanced transformer model has been developed in EMTP-RV Software. Subsequent simulations show that accurate modeling of the power transformer losses does only have minor influences on harmonic over-voltages damping. It is shown however that the usage of the proposed model is essential to predict adequately the risks of ferroresonance and generated over-voltages in power systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.