This paper discusses a three-and-one-half-year study of constantly energized 500 kV station-post insulator performance in a coastal environment where ocean salt, moderate industrial contaminant, and coastal fog are encountered. Under test at PG and E's Moss Landing EHV Laboratory are semiconductive, siliconed, and untreated porcelain glazed posts. Semiconductive and full length siliconed posts have not flashed over during the test period. Multiple flashovers of the untreated posts in nighttime fog have required summer hotwashing to allow continued testing.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.