Abstract
In this paper, we were analyzed the vibration characteristics of the three-phase cast resin transformer using less than 50% of load in the field. Most of the cast resin transformer is less than 50% in the domestic field is used for load conditions. Consisting of a solid insulator cast resin transformer is generating lots of noise and vibration. In addition, because it is affected by Joule’s heat is used in light load conditions. As a results, the transformer vibrations at frequencies below about from 200Hz to 500Hz were detected. Vibration velocity depends on the load variations were found. Load up to approximately 20-30% in most cases the vibration velocity was found at 4,000 ㎛/s or less, 8,000 ㎛/s or more. Vibration frequency at light load conditions were generated at the 120㎐, 240㎐, 360㎐ and 480㎐. At the load condition of from 10% to 20%, vibration velocity is higher than another. Most of the vibration velocity were identified at the 1,000 ㎛/s or less. Using the vibration frequency and velocity measurements data, the load on the cast resin transformer analyzed the correlation of the burden. Therefore, this data could be found in the vibration characteristics of the light-load conditions. If the field measurements using the data perform diagnostics on the transformer, it’s expected to be very effective.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Transactions of The Korean Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.