Abstract
In this paper, we studied the dielectric breakdown voltage characteristics by the AC withstand voltage test on using green insulation dry air instead of <TEX>$SF_6$</TEX> insulation gas used in the GIB (gas insulated bus) of 362 kV GIS (gas insulated switchgear). The AC withstand voltage test applied to the standard KEPCO's 362 kV GIB with dry air insulation, and the equivalence of dielectric breakdown voltage for dry air and <TEX>$SF_6$</TEX> gas were examined, and the empirical formulas of dielectric breakdown voltage for dry air were calculated, and the criterion of AC withstand voltage test for dry air insulation was derived. Using the criterion, dry air can be used instead of <TEX>$SF_6$</TEX> gas for 362 kV GIB in the factory acceptance test was confirmed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Institute of Electrical and Electronic Material Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.