Abstract

A transformer type superconducting fault current limiter (SFCL) is one of the fault current limiters which have been proposed to reduce the fault current in the transmission lines. This paper proposes the new circuit configuration of a transformer type SFCL and also investigates the operating characteristics of the transformer type SFCL containig the resistor in the tertiary winding. The proposed SFCL contains the resistor in the tertiary winding. The newly inserted resistor can divert the power which the High-Tc superconducting has to bear. Because the resistor in the tertiary winding relieves the power of the High-Tc superconducting, it is possible that the proposed transformer type SFCL can decrease the more larger fault current than the conventional SFCL with the same High-Tc superconducting. And the cost of the proposed transformer type SFCL can be reduced.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.