Abstract
This paper describe the 2 dimensional fully coupled analysis with EM field and thermal-fluid analysis using commercial software to predict the temperature distribution of the UHV Gas Insulated Bus (GIB). To perform the heat transfer simulation, sources are calculated in the ohmic loss of the conductor and eddy current loss of the enclosure by harmonic eddy current analysis. The emissivity and absorption coefficient are determined by experimental data and referred from references and the local hot spot are estimated by 3 dimensional coupled simulations. The actual 145kV three phases GIB was used for the experiment and temperature sensors were installed. The accuracy of the analysis is verified through the comparison of the simulation temperature result and experimented in UHV GIB.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.