Abstract

It is important to grasp whole velocity field and temperature field when evaluating air conditioning room environment. However it is difficult to obtain data of whole room even when we use PIV technique, except for a room model built for experimental purpose.In this report, we attempt to interpolate and correct measured data which is discrete and partial by using the governing equations of flow field. We excuted an experiment for an air conditioning room of 3-dimensional steady flow field including heat source, and measured velocity distribution by using PIV for smoke image and temperature by thermocouples. Subsequently, we estimated whole flow field from the obtained data and the governing equations by using GCFM (Generalized Cost Function Method) which reflects the information of measured data to the mutual estimation of each field.