Abstract
The superconducting magnets for the accelerator's rings will be cooled by a forced flow supercritical helium system from a central refrigeration plant. The design temperature for these magnets varies from 2.6 K to 3.8 K depending on a magnets location in the ring. This paper describes the forced flow cooling system for testing a prototype magnet near 2.6 K; this lowest temperature being of special interest to evaluate magnet quench protection. The test forced flow cooling system uses a three-stage approach, including an ejector pumped bath, similar to a cycle described previously. The coolant exists at 3.8 K from these first stages and is then cooled further in a 64 cm diameter by 3 m high shielded liquid helium dewar. The supercritical helium gas passes through a submerged copper coil in this bath which is pumped to a pressure of 65 mm absolute by a screw compressor system. Temperatures are measured by thermistors located in the gas stream, and also embedded in the magnet coil.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.