Abstract
An experimental study was made to elucidate critical heat flux(CHF) characteristics in a two-phase concentric-tube thermosyphon. The experiment was performed by using saturated water, over the experimental range of configuration: inner diameter of heated outer tube D= 12mm, outer diameter of unheated inner tube d_o=3 to 10mm and heated tube length L= 1 00 to 1000mm. The experiment shows that the CHF is enhanced with increase in the inner tube diameter, and that the CHF decreases beyond a certain diameter of the inner tube. There is an optimum diameter for inner tube that maximizes the CHF, for each tube length and test liquid. The CHF maximum is about two to eight times as large as that without an inner tube. For a large inner tube, the CHF characteristics is similar to that for natural convective boiling in a vertical annular tube.<br/>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Transactions of the Korean Society of Mechanical Engineers B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.