Abstract
Flowmeter, especially orifice flowmeter, is one of the most important devices in process industry. Since the most frequent problem of orifice flowmeter at the operation site is the impulse line blockage, the diagnostics of impulse line blockage is required. In this paper, the effectiveness of two diagnostic methods, based on the pressure fluctuation and based on the delay of pressure transmission, are demonstrated. Though both methods work well in the steady state, the diagnostic method based on pressure fluctuation is getting more difficult to diagnose the blockage with increase of the pressure change rate. On the other hand, the diagnostic method based on the delay of pressure transmission is not influenced by increase of the pressure change rate, however, this method needs more computing resource. Hence, it is necessary to choose the diagnostic method in consideration of computing resource of field device and pressure change rate.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.