Abstract

We confirmed the superiority of the flow of the new 3D-blades by Computational Fluid Dynamics(CFD) for the high efficiency of the turbofan for package air-conditioner indoor units. As a result, the new 3D-blade fan reduces the flow-separation at the leading-edge and blows out uniformly form the outlet of the fan. In addition decreasing of 15% of axis power by the CFD result, and reducing of fan motor input 11% by the actual machine evaluation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.