In this study, the fire source model was investigated to predict the damage of electric cable in fire accident. The Polyethylene based Eco-Material (EM) cables and heat/fire resistant Non-Halogen (NH) cables which were used in nuclear power plants were applied to the flammability tests. The cone calorimeter tests for EM cables and NH cables were conducted to evaluate relationship between ignition time and heat release rate(HRR). Two fire source models, the HRR model and the chemical reaction model in CFD simulation code(FDS5.0) were applied to represent the flammability tests results of multiple cables.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.