Abstract

Under the support of the China State Grid Corporation Science and Technology Project, a set of 10 kV superconducting fault current limiter (SFCL) with bias magnetic field including a high temperature superconducting a low inductance unit, a double split reactor, a fast breaker and its control system is designed and assembled in Hushitai high voltage center of Electric Power Research Institute of State Grid Liaoning Electric Power Co., Ltd. The 10 kV dedicated test including high voltage test, phase to phase short circuiting fault test, quench resistance measurement, quench recovery time measurement were performed in December 2019. The fault current distribution and voltage test results during the phase to phase short-circuit fault of the SFCL are presented and analyzed. Test results indicate that current limiting resistance of SFCL unit is about 1.21 Ω within 10 ms fault time. Those results meet the design requirement.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.