Abstract

In this study, nucleate boiling heat transfer coefficients (HTCs) of five flammable refrigerants of propylene (R1270), propane (R290), isobutane (R600a), butane (R600), and dimethylether (RE170) were measured at the liquid temperature of 7 °C on a low fin tube of 1023 fins per meter, Turbo-B, and Thermoexcel-E tubes. All data were taken from 80 to 10 kW m−2 with an interval of 10 kW m−2 in the decreasing order of heat flux. Flammable refrigerants' data showed a typical trend that nucleate boiling HTCs obtained on enhanced tubes also increase with the vapor pressure. Fluids with lower reduced pressure such as DME, isobutene, and butane took more advantage of the heat transfer enhancement mechanism of enhanced tubes than those with higher reduced pressure such as propylene and propane. Finally, Thermoexcel-E showed the highest heat transfer enhancement ratios of 2.3–9.4 among the tubes tested due to its sub-channels and re-entrant cavities.