Abstract

When small scale wind and solar power generation systems are connected to conventional power distribution system. It is worried that it can affect the quality of electricity such as voltage variation, power factor, frequency, harmonics and flicker. Therefore, in this research, in order to investigate the effects of wind power generation equipments(AC link method) on electrical power quality, when they are connected to distribution system. Power quality analyzer was installed respectively at the front side of power conversion system of conventional wind generation system and secondary side of consumer`s power supply at distribution line. Measurements on power quality were performed and the effects of the wind generation system on distribution system were analyzed when it was and was not operated. The results show that 0.34[%] increase on voltage variation, 0.145 increase on current crest factor and 0.6[] deviation on phase difference when the power generation system was operated.