Abstract
In this paper, cycle performance analysis of two-stage compression and one-stage expansion refrigeration system applied various refrigerants is presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include degree of superheating and subcooling, compressor efficiency, evaporation temperature, condensing temperature, mass flow rate ration into inter-cooler, effectiveness of internal heat exchanger. The main results were summarized as follows : The COP of two-stage compression and 1-stage expansion refrigeration system increases with the increasing subcooling, mass flow rate ration of inter-cooler, evaporation temperature, but decreases with the increasing condensing temperature and superheating degree. Therefore, subcooling degree, mass flow rate ratio of inter-cooler of two-stage compression and 1-stage expansion using substitute refrigerant have an effect on COP of this system. The COP of alternative refrigerants was higher than the COP of R22 in this study, although the COP of some mixed refrigerants were lower than COP of R22.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korea Society For Power System Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.