Abstract
The purpose of this research was to investigate the efficiency of coagulants dose after backwashing. The turbidity of initial effluent was high after backwashing in the rapid sand filtration and the high turbidity was almost removed by coagulants dose into filter-sand after backwashing. It was found that the turbidity of initial effluent was well removed by all kinds of the coagulants used in this study. When filtration was performed input water with differentiated pH's, the turbidity of effluent was low at the range of pH 5 - pH 7. But the removal was not good about over pH 9. This result was considered into the existence forms of aluminium, <TEX>$Al(OH)^{2+}\;and\;{Al(OH)_2}^+$</TEX> at pH 5. Cryptosporidiums of effluent were 4/ml for ten minutes immediately after back washing and 3/ml until sixty minutes. However, the case of coagulant dose after backwashing, Cryptosporidiums of effluent were 0.5/ml for ten minutes with no detection after twenty minutes.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.