Abstract

Heat pumps have received a fair amount of attention all over the world for their high efficiency and low environmental impact. Employing heat pumps for residential heating and cooling produces only about 2038 kg-<TEX>$CO_2$</TEX>/year, an amount which is less than half that of conventional boiler systems. However, the use of single-stage heat pumps becomes uneconomical when they are operated at very low evaporating temperature or high condensing temperature. Two-stage heat pumps systems can be used successfully for low or high temperature applications. In this paper, the experimental study on the performance of two-stage heat pump with an economizer was executed in heating mode. When the secondary fluid inlet temperature to the indoor heat exchanger increased, the COP enhancement rate of two-stage heat pump with an economizer was increased. For all outdoor inlet temperature conditions, the performance of the heat pump with an economizer was higher than it without an economizer.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call