Abstract

For the safe handling of n-pentadecane, the lower flash points and the upper flash point, fire point, AITs(auto-ignition temperatures) by ignition delay time were experimented. Also lower and upper explosion limits by using measured the lower and upper flash points for n-pentadecane were calculated. The lower flash points of n-pentadecane by using closed-cup tester were measured <TEX>$118^{\circ}C$</TEX> and <TEX>$122^{\circ}C$</TEX>. The lower flash points and fire point of n-pentadecane by using open cup tester were measured <TEX>$126^{\circ}C$</TEX> and <TEX>$127^{\circ}C$</TEX>, respectively. This study measured relationship between the AITs and the ignition delay times by using ASTM E659 apparatus for n-pentadecane. The experimental AIT of n-pentadecane was <TEX>$195^{\circ}C$</TEX>. The calculated lower and upper explosion limit by using measured lower <TEX>$118^{\circ}C$</TEX> and upper flash point <TEX>$174^{\circ}C$</TEX> for n-pentadecane were 0.54 Vol.% and 6.40 Vol.%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.