This paper dealt with the radiated electromagnetic wave detection of partial discharge (PD) in oil for insulation diagnostics of oil-immersed transformers. Three types of electrode system were fabricated to simulate the insulation defects that could occur in oil-immersed transformers. Frequency components of radiated electromagnetic wave in oil was measured by broadband bi-conical antennas of 300 MHz~2 GHz and a spectrum analyzer of 9 kHz~3 GHz. Frequency component of electromagnetic waves from PD in oil were highly distributed at 500 MHz. From the result, a narrow-band monopole antenna with the center frequency of 500 MHz was fabricated. We could detect PD signal in insulation oil without an influence of external noise by a measurement system which consists of the prototype monopole antenna, a LNA (Low Noise Amplifier), an oscilloscope and a spectrum analyzer.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Institute of Electrical and Electronic Material Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.