Abstract
This study investigated exploratory research on energy consumption model of elementary schools by using an explanatory variable, number of classes and responsive variable, total annual energy consumption. Totally 18,539 data set of energy consumption in elementary schools are acquired for the analysis. After excluding abnormal data, 18,363 data set was used for the least square method for number of classes and total annual energy consumption. As the result of the study, the developed linear regression model is as follow: Annual total energy consumption (TOE) = 2.6259•X + 15.5 (X: number of classes). The coefficient of determination of this model is 0.7336. The derived coefficient of determination is slightly lower than required value of 0.75 by ASHRAE 2013. However, considering various conditions of 18,363 elementary schools, the derived model is thought to be meaningful enough.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of The Korean Society of Living Environmental System
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.