Abstract

In this study, a cold aisle containment system was proposed among various strategies to reduce the energy waste by recirculation air from the hot aisle. To verify the effectiveness of the cold aisle containment system, a test bed which is similar to an actually existing server room was set up in the Internet Data Center(IDC) building. Comparative experiments, conventional open type cooling system and cold aisle containment system were carried out under actual conditions. The result revealed that the range of inlet temperature of the server system was <TEX>$20{\sim}25^{\circ}C$</TEX> in an existing cooling system and the range of inlet temperature dropped below <TEX>$20^{\circ}C$</TEX> by the cold aisle containment system. After all, cold aisle containment system was proved to be the solution for energy saving cooling system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.