In the article analysis technique of electromagnetic safety conditions on routes of
 compact power lines (CPL) is offered. As the tool the program complex Fazonord was applied to modeling of CPL modes and electromagnetic fields.
 Results of modeling show that the average levels of CPL electric field strengths exceed a similar indicator for the standard power line by 25…145 %, distinctions of maximums lie within 7… 150 %.
 Especially considerable strength excesses take place at three-segment CPL. By criterion of magnetic
 field strength the return picture is observed: levels of CPL magnetic field strength on 70 … 90 % below
 than in traditional power line, and the best picture of electromagnetic safety possesses the foursegment power line.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Scientific Papers Collection of the Angarsk State Technical University
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.