The fin and tube heat exchanger using a two-port tube has in air-conditioner heat exchanger because heat transfer performance. This study investigates the feasibility of a fin and tube heat exchanger using two-port copper tube by mechanical expansion. The optimum size of the tube-expanding bullet for the heat exchanger using two-port tube was through numerical calculation. The heat exchanger using a two-port tube was fabricated by mechanical expansion, and the heat exchanger performance was evaluated condensation and evaporation experiments. Compared to the heat exchanger of a conventional circular tube, the pressure drop per unit length of the heat exchanger with a two-port tube decreased. Compared to the heat exchanger using a conventional circular tube, the overall heat transfer coefficient of heat exchanger with a two-port tube increased up to 13% in the case of condensation, and up to 25% in the case of evaporation. The two-port tube heat exchanger outperforms conventional heat exchanger for air conditioner with a inner grooved circular tube.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Korean Journal of Air-Conditioning and Refrigeration Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.