Abstract

In Korea, summer is hot and humid, and air-conditioners consume too much electricity due to large amount of latent heat. Simultaneous usage of dehumidifier may reduce the latent heat and save the electricity. In this study, dehumidification performance was measured in a constant temperature and humidity chamber for a small-sized dehumdification rotor made of inorganic fiber impregnated with metallic silicate. Variables were rotor speed, room temperature, regeneration temperature, room relative humidity and frontal velocity to the rotor. Results showed that there existed optimum rotor speed (1.0 rpm), and optimum regeneration temperature (100 o C). Above the optimum rotor speed, incomplete regeneration is responsible for reduced dehumidification. Above the optimum regeneration temperature, increased temperature difference between regeneration and dehumidification process is responsible for reduced dehumidification. The amount of dehumidification also increases with the increase of relative humidity, dehumidification temperature and flow velocity into the rotor.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.