Abstract

This paper is aimed to analyze the characteristics of simultaneous voltage, current and temperature signals for poor connection on electrical connector. In order to attain this purpose, detected were the current and voltage signals on electric wire with series arc, named arc signals, and also monitored were the changes of RMS, instantaneous value of waveform in time domain and temperature value with video. Two states are made normal state over 5㎏f·㎝ and poor connections state below 0.5㎏f·㎝ by screw gage. In the voltage signal case, the voltage drop was increased with which the current was increased. In the current signal case, poor connections at the time interval 1~4A all showed shoulder, as distinct difference from the normal state shown waveform pattern. In the temperature signal case, poor connections are twice at 1A and five times at 4A in the normal state. The temperature continues insulation of electrical wiring and connector can be carbonized. The results of this study will be effectively used in developing the

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.