The paper presents the results of an analysis of harmonic active power at the nodes connecting a 220 kVsupply network to three nonlinear high-power loads: an aluminum smelter shop, a pulp and paper plant and a railway traction substation. The main process equipment of the facilities is a source of harmonics. The analysis is performed on the basis of measurements. Measured current and voltage were used to calculate active power for harmonics 2—40. Based on the analysis, it was found out that the facilities are the sources of characteristic harmonics and generate the harmonic active power to the network only during part of the measurement time. For the other part of the time the harmonic active power flows from the network to the load of the facilities. The values of the harmonic active power flowing in both directions vary from several tens of watts to several tens of kilowatts. The paper presents the proposals on the use of harmonic active energy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.