Abstract

In order to evaluate indoor air quality and ventilation effectiveness, it is necessary to comprehend properties of various ventilation systems. In this paper we describe the results of field measurement of ventilation effectiveness for four office rooms using age of air and air exchange effectiveness. The results are as follows. (1) In the case of air conditioning system and ventilation system using ceiling chamber for return air, the local air exchange effectiveness in the room is ranged from 0.8-1.2. (2) In the case of raised floor air supply system, the local air exchange effectiveness is ranged from 0.9-1.1, however in the case of ceiling supply chamber system is ranged from 0.8-1.0. (3) The room which is ventilated by duct system, local air exchange effectiveness becomes about 0.7-1.1. When supply outlets are closed to make bad ventilated area, local air exchange effectiveness of bad ventilated area becomes 0.8-1.0, in the other hand the release area of supply outlets becomes 1.0-1.1. (4) It is possible to evaluate ventilation characteristics of office space by local age of air and local air exchange effectiveness.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.