LDC(Line Drop Compensation) is widely used in controlling ULTC(Under Load Tap Changer) output voltage at distribution substation. However, LDC may experience some difficulties in voltage control due to renewable energy resources and distributed generations. Therefore, more advanced voltage control algorithm is necessary to deal with these problems. In this paper, a modified voltage control algorithm for ULTC and DG is suggested. ULTC is operated with the voltages measured at various points in distribution system and prevents overvoltage and undervoltage in the distribution feeders. Reactive power controller in DG compensates the voltage drop in each distribution feeders. By these algorithms, the voltage unbalance between feeders and voltage limit violation will be reduced and the voltage profile in each feeder will become more flat.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Transactions of The Korean Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.