Abstract

Power Fuses that are installed to protect for Voltage Transformer had been burnt out by operating environments, the characteristic of fuse and aging in power plants. To analyzes the root causes of fuse failures, this study reviews the appropriateness of the fuse selection according to the VT rating and capacity, the effects of inrush current that may occur during VT power up and the possibility of resonance due to poor VT excitation characteristics. In addition, the internal condition and the blown-off melt shape of the burned-out fuse were confirmed by the industrial X-ray, the electron microscope, and the material analysis.