On the site of water and sewage treatment facilities, in order to control and monitor not only distribution installed control equipment but also power equipment and lighting equipment, on-site control panels are installed in addition to a central monitoring and control system, to form an automatic control system. In particular, in order to comprehensively manage control power failures inside the on-site control panels, the prototype under development has additional features: a DC power abnormality monitoring device that monitors control power overload and arc discharge was developed, installed and applied to the on-site control panel, and an arc sensor, an infrared sensor, and a vibration sensor which are widely used across the industry were also installed to diagnose the integrity of the insulation inside the panel.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.