Abstract
This paper presents the novel voltage control method in power distribution system with distributed generators. The voltage in distribution systems is regulated by Under Load Tap Changer(ULTC) of substation and pole transformer of primary feeders. Recently, Step Voltage Regulator(SVR) is getting located at distribution feeders to regulate effectively voltage of primary feeders. But the effectiveness of SVR decreases due to independent operation between SVR and ULTC, and also the existing Line Drop Compensator(LDC) method considering the distributed generators may be not able to regulate the proper voltage in a permissible range. Thus, this paper presents a optimal voltage control algorithm of SVR by using the secondary voltage data of main transformer in substation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Transactions of The Korean Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.