Abstract

This paper describes the performance comparison results for current controller of a single-phase PFC converter with 1-switch voltage doubler strategy for single-phase double-conversion UPS(Uninterruptible Power Supply). A single-phase PFC converter with 1-switch voltage doubler strategy needs a diode bridge and one bidirectional active switch. Thus it is possible to reduce the material cost. However, the study results of current controller design and comparison of current control method has not been known after the converter circuit was proposed. For the performance comparison of current control, single-phase 3 kVA double-conversion UPS was tested. The performance of PI and PR current controller is experimentally confirmed with followings - input current reference tracking, input power factor correction and input current THD suppression.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.