Abstract

This study focuses on model identification and a 2-DOF PID control algorithm for cooling processes; a pneumatic butterfly-type control valve is used for this purpose. The mathematical model is a transfer function composed of a time delay and a second-order delay system. The control valve is identified as a first-order delay system with a time delay and included in the controlled plant. From the experimental data sets for a demo plant, the model parameters are identified, and the 2-DOF PID control gains are analytically derived by Kitamori's method. We show via a computer simulation and an experimental test that the performance of the proposed 2-DOF PID control system is better than that of a conventional 1-DOF PID control system.